Posted by Doug L on May 6, 2006, 12:25 am
If you were  Registered and logged in, you could reply and use other advanced thread options
You took part of James response out of context, while he stated that you
would only need one reversing relay to activate the sounders, he also
clearly stated that you would still need a supervision relay for each zone.

The complete text of his reponse is quoted below

"You only need one RRS module on the smoke detector power wires. Even
though
you have zoned out the smokes they will all use the same power source so 1
relay is good. You will need one end of line supervision relay for each
zone (18) of them. The reversal relay should be wired to a fire alarm
bell/siren output. I would not use the sounders in the smoke detectors for
burglary, although it is possible. James B"

Doug L

--

>> Even though you have zoned out the smokes they will all use the same
>> power source so 1 relay is good.
>
> Using 1 power supervision module at the control will only supervise the
> power supply itself- it will do nothing to supervise the wiring. The
> proper way to supervise power on 4 wire smokes is an EOL power supv relay.
> In this case, 18 of them...
>



Posted by stormy2084 on May 3, 2006, 11:05 am
If you were  Registered and logged in, you could reply and use other advanced thread options
A big thanks to all of you for all the very helpful information.


Similar ThreadsPosted
Apollo 30 smoke detector wiring October 9, 2005, 8:56 am
Smoke detector question August 23, 2005, 8:35 am
smoke detector recommendation April 7, 2008, 2:44 pm
Smoke detector and rechargeable 9V battery? November 25, 2006, 7:06 pm
2 or 4 wire smoke detector question. July 18, 2007, 7:28 am
Tyco smoke detector recall May 25, 2006, 9:20 pm
need help to reset 449CST wireless smoke detector June 27, 2006, 10:52 pm
Have Your Installed Smoke Detector In Home/Office March 26, 2008, 4:32 am
Have Your Installed Smoke Detector In Home/Office March 26, 2008, 4:33 am
2 Partition DSC 1864 Smoke Detector Question June 28, 2008, 3:31 am

The site map in XML format XML site map

Contact Us | Privacy Policy