Can't address pull stationsight 5808 on Silent Knight panel. paul@resi-tech.com 03-21-2008
Posted by paul@resi-tech.com on March 21, 2008, 7:49 pm
If you were  Registered and logged in, you could reply and use other advanced thread options
> secure15 wrote:
> >> Ok Genius responder,
> >> I already figured the pulls out. =A0I used the dip switches to program
> >> them. =A0I still need to know how to program the smokes. =A0They don't
> >> have dip switches!!!
> > Any "Genius" tech who goes out into the field with a New Panel and
> > doesn't know how to program it .........???????
> > Who wants to hold his hand????
>
> Maybe he didn't have a choice. (employer says: "Here, go install this
> today.")
> Having a bad day Mike? =A0:-)
>
> --
> js
>
> He who laughs last.......thinks the slowest

OK Secure15,

1. I am not in the field. I am setting the panel up in the office
BEFORE I take it out for install.
2. I have never installed a Silent Knight Panel.
3. The only reason I posted for help is because tech support is
closed today.
4. I don't care for your sacarasm (genius referance)

5. If you don't have something positive to contribute why don't you
just not respond?
Why go out of your way to insult someone who is simply asking if
anyone can help.

Since you didn't respond about the smoke detector, I assume you don't
know either.

Posted by Just Some Guy on March 21, 2008, 8:21 pm
If you were  Registered and logged in, you could reply and use other advanced thread options
Wire up a base to the SLC program terminals. Insert a new smoke detector in
the base and use the front panel menu to "assign" it an address. Repeat as
necessary using a different unused address for every new smoke. The SLC
program terminals are only intended to assigning addresses to smokes/heats.
You connect the field wiring to the SLC out terminals.

Pulls, monitor modules, control modules, etc get their addresses via dip
switches.

We like to leave a base connected to the program terminals in case a tech
needs to add or replace a smoke.

PS I hate SK addressable panels and consider them junk.


> secure15 wrote:
> >> Ok Genius responder,
> >> I already figured the pulls out. I used the dip switches to program
> >> them. I still need to know how to program the smokes. They don't
> >> have dip switches!!!
> > Any "Genius" tech who goes out into the field with a New Panel and
> > doesn't know how to program it .........???????
> > Who wants to hold his hand????
>
> Maybe he didn't have a choice. (employer says: "Here, go install this
> today.")
> Having a bad day Mike? :-)
>
> --
> js
>
> He who laughs last.......thinks the slowest

OK Secure15,

1. I am not in the field. I am setting the panel up in the office
BEFORE I take it out for install.
2. I have never installed a Silent Knight Panel.
3. The only reason I posted for help is because tech support is
closed today.
4. I don't care for your sacarasm (genius referance)

5. If you don't have something positive to contribute why don't you
just not respond?
Why go out of your way to insult someone who is simply asking if
anyone can help.

Since you didn't respond about the smoke detector, I assume you don't
know either.



Posted by Doug on March 21, 2008, 10:13 pm
If you were  Registered and logged in, you could reply and use other advanced thread options

> Wire up a base to the SLC program terminals. Insert a new smoke detector
> in the base and use the front panel menu to "assign" it an address.
> Repeat as necessary using a different unused address for every new smoke.
> The SLC program terminals are only intended to assigning addresses to
> smokes/heats. You connect the field wiring to the SLC out terminals.
>
> Pulls, monitor modules, control modules, etc get their addresses via dip
> switches.
>
> We like to leave a base connected to the program terminals in case a tech
> needs to add or replace a smoke.
>
> PS I hate SK addressable panels and consider them junk.
>
>

I use the SK addressable panels for most of the Fire jobs I do, I've had no
real problems with them, What problems have you had that make you consider
them junk?

Doug



Posted by Just Looking on March 21, 2008, 11:17 pm
If you were  Registered and logged in, you could reply and use other advanced thread options
>PS I hate SK addressable panels and consider them junk.

Any you know that get a non junk rating? The only fire panels I see
regularly are the Bosch 7024. Good for small jobs. They are just
addressable, not analog addressable.

> Wire up a base to the SLC program terminals. Insert a new smoke detector
in
> the base and use the front panel menu to "assign" it an address. Repeat
as
> necessary using a different unused address for every new smoke. The SLC
> program terminals are only intended to assigning addresses to
smokes/heats.
> You connect the field wiring to the SLC out terminals.
>
> Pulls, monitor modules, control modules, etc get their addresses via dip
> switches.
>
> We like to leave a base connected to the program terminals in case a tech
> needs to add or replace a smoke.
>
> PS I hate SK addressable panels and consider them junk.
>
>
> > secure15 wrote:
> > >> Ok Genius responder,
> > >> I already figured the pulls out. I used the dip switches to program
> > >> them. I still need to know how to program the smokes. They don't
> > >> have dip switches!!!
> > > Any "Genius" tech who goes out into the field with a New Panel and
> > > doesn't know how to program it .........???????
> > > Who wants to hold his hand????
> >
> > Maybe he didn't have a choice. (employer says: "Here, go install this
> > today.")
> > Having a bad day Mike? :-)
> >
> > --
> > js
> >
> > He who laughs last.......thinks the slowest
>
> OK Secure15,
>
> 1. I am not in the field. I am setting the panel up in the office
> BEFORE I take it out for install.
> 2. I have never installed a Silent Knight Panel.
> 3. The only reason I posted for help is because tech support is
> closed today.
> 4. I don't care for your sacarasm (genius referance)
>
> 5. If you don't have something positive to contribute why don't you
> just not respond?
> Why go out of your way to insult someone who is simply asking if
> anyone can help.
>
> Since you didn't respond about the smoke detector, I assume you don't
> know either.
>
>



Posted by secure15 on March 24, 2008, 2:57 pm
If you were  Registered and logged in, you could reply and use other advanced thread options
paul@resi-tech.com wrote:
>> secure15 wrote:
>>>> Ok Genius responder,
>>>> I already figured the pulls out. I used the dip switches to program
>>>> them. I still need to know how to program the smokes. They don't
>>>> have dip switches!!!
>>> Any "Genius" tech who goes out into the field with a New Panel and
>>> doesn't know how to program it .........???????
>>> Who wants to hold his hand????
>> Maybe he didn't have a choice. (employer says: "Here, go install this
>> today.")
>> Having a bad day Mike? :-)
>>
>> --
>> js
>>
>> He who laughs last.......thinks the slowest
>
> OK Secure15,
>
> 1. I am not in the field. I am setting the panel up in the office
> BEFORE I take it out for install.
> 2. I have never installed a Silent Knight Panel.
> 3. The only reason I posted for help is because tech support is
> closed today.
> 4. I don't care for your sacarasm (genius referance)
>
> 5. If you don't have something positive to contribute why don't you
> just not respond?
> Why go out of your way to insult someone who is simply asking if
> anyone can help.
>
> Since you didn't respond about the smoke detector, I assume you don't
> know either.
I don't give a shit where you are setting it up.
I can tell you never installed one
I don't care if you care about my sarcasm
Positive contribution? Who the fuck made you the King?
Don't assume I don't know about the smokes---I do>
GO FUCK OFF!

Similar ThreadsPosted
Problems I had with Silent Knight 5808 addressing March 27, 2008, 8:21 am
Silent Knight November 4, 2005, 9:56 am
Silent Knight 4724 October 7, 2005, 10:41 pm
Silent Knight 5104 August 22, 2006, 7:04 pm
Silent Knight 5104 August 24, 2006, 9:16 pm
WTB: Silent Knight 7150 January 30, 2007, 10:31 pm
Need a Silent Knight 5205 September 13, 2007, 2:21 pm
Re: Silent Knight 2615 February 12, 2008, 7:58 pm
Silent Knight 9800 Reciever July 11, 2005, 11:48 am
5540 Software - Silent Knight September 6, 2005, 1:05 am

The site map in XML format XML site map

Contact Us | Privacy Policy