Can't address pull stationsight 5808 on Silent Knight panel.

Can't address pull stationsight 5808 on Silent Knight panel.

Secure Home | Search | About
 CCTV, Alarms and other Physical Security    Post an article   get this group's latest topics as an RSS feed add this group's latest topics to your My MSN content add this group's latest topics to your My Yahoo content add this group's latest topics to your Google content
Subject Author Date
Can't address pull stationsight 5808 on Silent Knight panel. paul@resi-tech.com 03-21-2008
Posted by Frank Olson on March 21, 2008, 5:02 pm
If you were  Registered and logged in, you could reply and use other advanced thread options
paul@resi-tech.com wrote:
> On Mar 21, 2:55 pm, Frank Olson
>> p...@resi-tech.com wrote:
>>>> Can't address pull stationsight 5808 on silent Knight panel.
>>>> Boy, am I frustrated!!.. Manual says just hook unit to 2 terminals
>>>> named SLC program, follow menu instructions and the unit is
>>>> programmed. I keep getting "connecting to device" but it never does!!
>>>> What am I doing wrong?
>>>> I have the correct +on SLC on panel and SLC on Unit.
>>>> I have the pull station address set for 1.
>>>> Any suggestions for what I can do?
>>>> PS Silent Knight tech support closed for Easter today. Thanks
>>> Model number of pull station is SD 500 Ps
>>> This is a new panel. I am tryiny to set 1 pullstation to address 1.
>>> I have verified correct polarity
>>> The panel has 3 sets of SLC terminals.
>>> ...SLC in (I am not using)
>>> ...SLC out (I am not using at this time. Manual sys to connect to SLC
>>> Program to address)
>>> ...SLC Program. IO am using these terminals
>>> Side Note: I do not have voltage at SLC Program terminals but I do
>>> have voltage on SLC Progam terminals
>> Connect the pull station to the SLC "out" terminals. Observe proper
>> polarity. You won't have a problem.- Hide quoted text -
>>
>> - Show quoted text -
>
> Sorry Frank, that doesn's work either.
>
> All I need to do is set the address on 16 smoke detectors SD 505 APs
> And 13 Pullstations SD 500 Ps.
> Manual says connect to SLC Program terminals and follow menu to set
> address.
> Keeps saying " No device found " when I try to read it or
> "Connecting" when I try to write it.
> I have wasted all day on this problem. AAAAAAAA!!!!!!!!!!!


Any way for you to send me the manual?

Posted by secure15 on March 21, 2008, 5:28 pm
If you were  Registered and logged in, you could reply and use other advanced thread options
Genius.....
You Don't "address" SK pull Stations via the SLC program Port on the Panel!
They are either made as a Standard Pull with NO SD500 MIM (mini input
module) or With the MIM preinstalled on the back of the Pull. If it's
not there,
You need to provide MIM for each of your Pulls -----UNLESS they are
preinstalled with the Pull---- There is NO DATA being sent from an SK
pull--- they are merely Point Addressable Inititating Devices---
Programmed via the "DIPS" on the MIM!



Frank Olson wrote:
> paul@resi-tech.com wrote:
>> On Mar 21, 2:55 pm, Frank Olson
>>> p...@resi-tech.com wrote:
>>>>> Can't address pull stationsight 5808 on silent Knight panel.
>>>>> Boy, am I frustrated!!.. Manual says just hook unit to 2 terminals
>>>>> named SLC program, follow menu instructions and the unit is
>>>>> programmed. I keep getting "connecting to device" but it never does!!
>>>>> What am I doing wrong?
>>>>> I have the correct +on SLC on panel and SLC on Unit.
>>>>> I have the pull station address set for 1.
>>>>> Any suggestions for what I can do?
>>>>> PS Silent Knight tech support closed for Easter today. Thanks
>>>> Model number of pull station is SD 500 Ps
>>>> This is a new panel. I am tryiny to set 1 pullstation to address 1.
>>>> I have verified correct polarity
>>>> The panel has 3 sets of SLC terminals.
>>>> ...SLC in (I am not using)
>>>> ...SLC out (I am not using at this time. Manual sys to connect to SLC
>>>> Program to address)
>>>> ...SLC Program. IO am using these terminals
>>>> Side Note: I do not have voltage at SLC Program terminals but I do
>>>> have voltage on SLC Progam terminals
>>> Connect the pull station to the SLC "out" terminals. Observe proper
>>> polarity. You won't have a problem.- Hide quoted text -
>>>
>>> - Show quoted text -
>>
>> Sorry Frank, that doesn's work either.
>>
>> All I need to do is set the address on 16 smoke detectors SD 505 APs
>> And 13 Pullstations SD 500 Ps.
>> Manual says connect to SLC Program terminals and follow menu to set
>> address.
>> Keeps saying " No device found " when I try to read it or
>> "Connecting" when I try to write it.
>> I have wasted all day on this problem. AAAAAAAA!!!!!!!!!!!
>
>
> Any way for you to send me the manual?

Posted by paul@resi-tech.com on March 21, 2008, 6:00 pm
If you were  Registered and logged in, you could reply and use other advanced thread options
> Genius.....
> You Don't "address" SK pull Stations via the SLC program Port on the Panel=
!
> They are either made as a Standard Pull with NO SD500 MIM (mini input
> module) or With the MIM preinstalled on the back of the Pull. If it's
> not there,
> You need to provide MIM for each of your Pulls -----UNLESS they are
> preinstalled with the Pull---- There is NO DATA being sent from an SK
> pull--- they are merely Point Addressable Inititating Devices---
> Programmed via the "DIPS" on the MIM!
>
>
>
> Frank Olson wrote:
> > p...@resi-tech.com wrote:
> >> On Mar 21, 2:55 pm, Frank Olson
> >>> p...@resi-tech.com wrote:
> >>>>> Can't address pull stationsight 5808 on silent Knight panel.
> >>>>> Boy, am I frustrated!!.. =A0 =A0Manual says just hook unit to 2 term=
inals
> >>>>> named SLC program, =A0follow menu instructions and the unit is
> >>>>> programmed. =A0I keep getting "connecting to device" but it never do=
es!!
> >>>>> What am I doing wrong?
> >>>>> I have the correct +on SLC on panel and SLC on Unit.
> >>>>> I have the pull station address set for 1.
> >>>>> Any suggestions for what I can do?
> >>>>> PS =A0Silent Knight tech support closed for Easter today. =A0 Thanks=

> >>>> Model number of pull station is SD 500 Ps
> >>>> This is a new panel. I am tryiny to set 1 pullstation to address 1.
> >>>> I have verified correct polarity
> >>>> The panel has 3 sets of SLC terminals.
> >>>> ...SLC in =A0(I am not using)
> >>>> ...SLC out (I am not using at this time. =A0Manual sys to connect to =
SLC
> >>>> Program to address)
> >>>> ...SLC Program. =A0IO am using these terminals
> >>>> =A0 =A0Side Note: I do not have voltage at SLC Program terminals but =
I do
> >>>> have voltage on SLC Progam terminals
> >>> Connect the pull station to the SLC "out" terminals. =A0Observe proper=

> >>> polarity. =A0You won't have a problem.- Hide quoted text -
>
> >>> - Show quoted text -
>
> >> Sorry Frank, that doesn's work either.
>
> >> All I need to do is set the address on 16 smoke detectors SD 505 APs
> >> And 13 Pullstations SD 500 Ps.
> >> Manual says connect to SLC Program terminals and follow menu to set
> >> address.
> >> Keeps saying " No device found " =A0when I try to read it or
> >> "Connecting" when I try to write it.
> >> I have wasted all day on this problem. =A0AAAAAAAA!!!!!!!!!!!
>
> > Any way for you to send me the manual?- Hide quoted text -
>
> - Show quoted text -

Ok Genius responder,
I already figured the pulls out. I used the dip switches to program
them. I still need to know how to program the smokes. They don't
have dip switches!!!

Posted by secure15 on March 21, 2008, 6:42 pm
If you were  Registered and logged in, you could reply and use other advanced thread options
paul@resi-tech.com wrote:
>> Genius.....
>> You Don't "address" SK pull Stations via the SLC program Port on the Panel!
>> They are either made as a Standard Pull with NO SD500 MIM (mini input
>> module) or With the MIM preinstalled on the back of the Pull. If it's
>> not there,
>> You need to provide MIM for each of your Pulls -----UNLESS they are
>> preinstalled with the Pull---- There is NO DATA being sent from an SK
>> pull--- they are merely Point Addressable Inititating Devices---
>> Programmed via the "DIPS" on the MIM!
>>
>>
>>
>> Frank Olson wrote:
>>> p...@resi-tech.com wrote:
>>>> On Mar 21, 2:55 pm, Frank Olson
>>>>> p...@resi-tech.com wrote:
>>>>>>> Can't address pull stationsight 5808 on silent Knight panel.
>>>>>>> Boy, am I frustrated!!.. Manual says just hook unit to 2 terminals
>>>>>>> named SLC program, follow menu instructions and the unit is
>>>>>>> programmed. I keep getting "connecting to device" but it never does!!
>>>>>>> What am I doing wrong?
>>>>>>> I have the correct +on SLC on panel and SLC on Unit.
>>>>>>> I have the pull station address set for 1.
>>>>>>> Any suggestions for what I can do?
>>>>>>> PS Silent Knight tech support closed for Easter today. Thanks
>>>>>> Model number of pull station is SD 500 Ps
>>>>>> This is a new panel. I am tryiny to set 1 pullstation to address 1.
>>>>>> I have verified correct polarity
>>>>>> The panel has 3 sets of SLC terminals.
>>>>>> ...SLC in (I am not using)
>>>>>> ...SLC out (I am not using at this time. Manual sys to connect to SLC
>>>>>> Program to address)
>>>>>> ...SLC Program. IO am using these terminals
>>>>>> Side Note: I do not have voltage at SLC Program terminals but I do
>>>>>> have voltage on SLC Progam terminals
>>>>> Connect the pull station to the SLC "out" terminals. Observe proper
>>>>> polarity. You won't have a problem.- Hide quoted text -
>>>>> - Show quoted text -
>>>> Sorry Frank, that doesn's work either.
>>>> All I need to do is set the address on 16 smoke detectors SD 505 APs
>>>> And 13 Pullstations SD 500 Ps.
>>>> Manual says connect to SLC Program terminals and follow menu to set
>>>> address.
>>>> Keeps saying " No device found " when I try to read it or
>>>> "Connecting" when I try to write it.
>>>> I have wasted all day on this problem. AAAAAAAA!!!!!!!!!!!
>>> Any way for you to send me the manual?- Hide quoted text -
>> - Show quoted text -
>
> Ok Genius responder,
> I already figured the pulls out. I used the dip switches to program
> them. I still need to know how to program the smokes. They don't
> have dip switches!!!
Any "Genius" tech who goes out into the field with a New Panel and
doesn't know how to program it .........???????
Who wants to hold his hand????

Posted by alarman on March 21, 2008, 7:30 pm
If you were  Registered and logged in, you could reply and use other advanced thread options
secure15 wrote:
>> Ok Genius responder,
>> I already figured the pulls out. I used the dip switches to program
>> them. I still need to know how to program the smokes. They don't
>> have dip switches!!!
> Any "Genius" tech who goes out into the field with a New Panel and
> doesn't know how to program it .........???????
> Who wants to hold his hand????

Maybe he didn't have a choice. (employer says: "Here, go install this
today.")
Having a bad day Mike? :-)

--
js

He who laughs last.......thinks the slowest



Similar ThreadsPosted
Problems I had with Silent Knight 5808 addressing March 27, 2008, 8:21 am
Silent Knight November 4, 2005, 9:56 am
Silent Knight 4724 October 7, 2005, 10:41 pm
Silent Knight 5104 August 22, 2006, 7:04 pm
Silent Knight 5104 August 24, 2006, 9:16 pm
WTB: Silent Knight 7150 January 30, 2007, 10:31 pm
Need a Silent Knight 5205 September 13, 2007, 2:21 pm
Re: Silent Knight 2615 February 12, 2008, 7:58 pm
Silent Knight 9800 Reciever July 11, 2005, 11:48 am
5540 Software - Silent Knight September 6, 2005, 1:05 am

The site map in XML format XML site map

Contact Us | Privacy Policy